RP, Double Check or PVB: Which Device Is Right?

Side-by-side comparison of the common assembly types, the hazards each is approved for, and installation rules.

The right assembly depends on the hazard. An RP is required for high-hazard connections that could carry toxic contaminants. A double check is approved for lower-hazard connections that would only affect taste or appearance. A PVB or SVB protects against backsiphonage only, so it's common on irrigation but can't be used where backpressure is possible. Your water district makes the final call.

Side-by-side comparison

RP (RPZ)Double check (DC)PVB / SVB
Hazard levelHigh (health hazard)Low (non-health hazard)High or low, backsiphonage only
Protects againstBacksiphonage and backpressureBacksiphonage and backpressureBacksiphonage only
How it worksTwo checks with a relief valve between themTwo independent checksOne check plus an air inlet
Typical usesMedical/dental, restaurants, car washes, chemical-injection irrigation, industrialFire sprinkler services, some commercial and residential servicesLawn and landscape irrigation
Installation ruleAbove grade, never in a pit; relief valve needs drainageCan be below grade where allowed, with test accessAt least 12 in. above the highest downstream outlet
Discharges water?Yes, when relief valve opensNoPVB can spit at startup; SVB is designed not to

How to tell which one you have

  • RP: look for a drain opening on the underside, between the two checks. It has four small test valves.
  • Double check: two check sections in a row and four test valves, but no drain opening underneath.
  • PVB/SVB: one body sitting up on a pipe, with a cap on top where air gets in and two test valves.

Can I switch types?

You'll need your district's OK. Going from an RP down to a double check almost never gets approved, but moving up is common when a building changes use. We do these as a replacement or new install.

Testing differences

Every type must be tested annually, but the procedures differ. An RP test checks the relief valve opening point and both checks. A double check test confirms each check holds. A PVB test checks the air inlet and the check. Details are on our testing page.

Related questions

Is an RPZ the same as an RP?

Yes. RPZ (reduced pressure zone) and RP (reduced pressure principle) refer to the same type of assembly.

How often do I need a backflow test?

Once a year at minimum. A device also needs testing right after it's installed, repaired or moved. Your water district picks the due date and normally mails a reminder ahead of time.

Have a notice from your district?

Same-week appointments. We handle the paperwork.

Call NowSchedule